boiler over pressuring

 
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Plumber
Author Message
kdflan



Joined: 11 Apr 2008
Posts: 25
Location: birmingham england

PostPosted: Tue Apr 22, 2008 7:30 pm    Post subject: boiler over pressuring Reply with quote

hi guys . got a problem with a vokera compact boiler . the boiler keeps over pressurising and the owner has to drain down the system every day virtualy . i was told it may be the filling loop passing water but have disconnected this and it has not passed water . any ideas would be grateful. thanks.
Back to top
AlanE
Moderator


Joined: 29 Jun 2003
Posts: 1318
Location: Colchester Essex

PostPosted: Tue Apr 22, 2008 7:40 pm    Post subject: Reply with quote

Defective heat exchanger. Job for a CORGI registered engineer.
Back to top
kdflan



Joined: 11 Apr 2008
Posts: 25
Location: birmingham england

PostPosted: Thu May 29, 2008 5:44 pm    Post subject: Reply with quote

reference boiler over pressurising , is it definetely faulty heat exchanger or could there be another fault as corgi engineer coming out and want to make sure i dont get hoodwinked thanks .the boiler is a vokera compact
Back to top
AlanE
Moderator


Joined: 29 Jun 2003
Posts: 1318
Location: Colchester Essex

PostPosted: Thu May 29, 2008 9:13 pm    Post subject: Reply with quote

Impossible to be 100% BUT if you say you have disconnected the filling loop then unless somewhere along the line you either have a cross connected pipe OR you also have a hot water cylinder on your system it only leaves the heatexchanger.

The Vokera Compact uses a combined main and DHE so there is not the normal plate heat exchanger in your boiler.

So as I said unless you have anything 'unconventional' in your combi system nothing else is left!