Waterworks
Joined: 14 Apr 2008 Posts: 2 Location: Hertfordshire
|
Posted: Mon Apr 14, 2008 11:18 am Post subject: No hot water & no heating - but boiler is working! |
|
|
Boiler, pump and diversion valve all work ok
Hot water not getting to radiators
There is water in the hot water tank
It seems there is no water or air in the radiators when the bleed valve is opened
What is wrong???
Hot water working through immersion.
Please help!!!! |
|
| Back to top |
|
 |
AlanE Moderator
Joined: 29 Jun 2003 Posts: 1305 Location: Colchester Essex
|
Posted: Mon Apr 14, 2008 11:38 am Post subject: |
|
|
That is an excellent question but impossible to answer with the information supplied!!
Boiler, pump and diversion valve all work ok
In which case where is the heat going to?
It seems there is no water or air in the radiators when the bleed valve is opened
What does happen if you open a bleed valve?
Need
Type of system - Sealed/open vented
How long does boiler run for
Make model of boiler
If system is open vented I would be thinking blocked cold feed, but that is reall just guesswork at this time. |
|
| Back to top |
|
 |
Waterworks
Joined: 14 Apr 2008 Posts: 2 Location: Hertfordshire
|
Posted: Mon Apr 14, 2008 1:42 pm Post subject: Diverter Valve |
|
|
The pipes get hot up to the valve but are cold from the other end of the cylinder coil. Could it be a blockage at the diverter valve?
Type of system - Sealed/open vented -- open vented
How long does boiler run for – about a minute
Make model of boiler – don’t know (will find out!) |
|
| Back to top |
|
 |
AlanE Moderator
Joined: 29 Jun 2003 Posts: 1305 Location: Colchester Essex
|
Posted: Mon Apr 14, 2008 4:17 pm Post subject: |
|
|
Try draining some water out of the system then check if the F&E tank level drops. If it doesn't there is probably a blockage in the cold feed.
Boiler is only operating to heat water in the pipes. You have little or no circulation. |
|