3kw pool heater mcb problem

 
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Electrician
Author Message
gaznod



Joined: 21 Aug 2005
Posts: 2
Location: Rochford, essex

PostPosted: Sun Aug 21, 2005 8:43 am    Post subject: 3kw pool heater mcb problem Reply with quote

Hi,

I want to plug a 3kw pool heater in to a socket in my garage. The garage is on a mk B16 mcb in the main fusebox, which is on the rcd side. The only other device on this circuit is the pool pump which is 55w. The garage circuit is a single 2.5mm2 twin and earth cable that runs for about 15-20 feet and is terminated in the garage by a fused box (not fusebox)

This wiring was present when i purchased the house.

Problem: when i plugged in the heater, the mcb made an awful humming/buzzing noise and eventually tripped. (happened after about 2 hours) but did not throw the rcd.

The manufacturer of the heater says it is suitable for plugging into a normal socket.

Any help would be great.

Thanks Gary
Back to top
gaznod



Joined: 21 Aug 2005
Posts: 2
Location: Rochford, essex

PostPosted: Sun Aug 21, 2005 5:23 pm    Post subject: Reply with quote

All sorted. The neutral wire in the Mcb was not tightened and was very loose. Checked all the connections and it works fine now.

Cheers Gary