| Author |
Message |
kdflan
Joined: 11 Apr 2008 Posts: 12 Location: birmingham england
|
Posted: Tue Apr 22, 2008 8:30 pm Post subject: boiler over pressuring |
|
|
| hi guys . got a problem with a vokera compact boiler . the boiler keeps over pressurising and the owner has to drain down the system every day virtualy . i was told it may be the filling loop passing water but have disconnected this and it has not passed water . any ideas would be grateful. thanks. |
|
| Back to top |
|
 |
AlanE Moderator
Joined: 29 Jun 2003 Posts: 1232 Location: Colchester Essex
|
Posted: Tue Apr 22, 2008 8:40 pm Post subject: |
|
|
| Defective heat exchanger. Job for a CORGI registered engineer. |
|
| Back to top |
|
 |
kdflan
Joined: 11 Apr 2008 Posts: 12 Location: birmingham england
|
Posted: Thu May 29, 2008 6:44 pm Post subject: |
|
|
| reference boiler over pressurising , is it definetely faulty heat exchanger or could there be another fault as corgi engineer coming out and want to make sure i dont get hoodwinked thanks .the boiler is a vokera compact |
|
| Back to top |
|
 |
AlanE Moderator
Joined: 29 Jun 2003 Posts: 1232 Location: Colchester Essex
|
Posted: Thu May 29, 2008 10:13 pm Post subject: |
|
|
Impossible to be 100% BUT if you say you have disconnected the filling loop then unless somewhere along the line you either have a cross connected pipe OR you also have a hot water cylinder on your system it only leaves the heatexchanger.
The Vokera Compact uses a combined main and DHE so there is not the normal plate heat exchanger in your boiler.
So as I said unless you have anything 'unconventional' in your combi system nothing else is left! |
|
| Back to top |
|
 |
|