Glow Worm Micron 40 FF

 
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Plumber
Author Message
guntony



Joined: 23 May 2008
Posts: 7
Location: Hertfordshire

PostPosted: Fri May 23, 2008 6:31 pm    Post subject: Glow Worm Micron 40 FF Reply with quote

Hi all,
I've got problems with my boiler. It run fine for about thirty minutes and got everything nice and warm then shut down. The pump runs when there is a demand for heat or water but the boiler doesn't come to life, the fan doesn't run so nothing else works from then. Any ideas....? Any help is much appreciated.....
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4755
Location: Bath

PostPosted: Sat May 24, 2008 9:40 am    Post subject: Reply with quote

The boiler has a set start up procedure;

You need to follow the manual and post what happens before it stops.
E>G> how many neons are lit, pump running, fan running. electric on and fuses ok
Back to top
guntony



Joined: 23 May 2008
Posts: 7
Location: Hertfordshire

PostPosted: Sat May 24, 2008 12:36 pm    Post subject: Reply with quote

Thanks for reply,
My main problem was the lack of manufacturers instructions but have now managed to download a copy which has helped a good deal.
Only the 1st neon is lit and manufacturers instructions pointed to testing the resistance of the thermistor which was within their spec, which according to them points to the pcb being faulty. I do hope that is the problem as I've already started trying to source a new one.
Thanks again for your time
Guntony....
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4755
Location: Bath

PostPosted: Sat May 24, 2008 1:04 pm    Post subject: Reply with quote

AlanE will be along later, so hang on till he posts.
Back to top
AlanE
Moderator


Joined: 29 Jun 2003
Posts: 1418
Location: Colchester Essex

PostPosted: Sat May 24, 2008 6:08 pm    Post subject: Reply with quote

If you have the PCB that has 6 neons then the chances are that the board is the problem.

Glowworm had problems with this board and was redesigned (twice??) so the replacement looks different. Also there are only two neons now.

Make sure you get the correct one as there is one for the smaller boilers without pump overrun and another for those boilers with overrun.

NOTE: Just thought this PCB also fits the Hideaway so make sure the 'jumper' on board is set correctly as per instructions that come with it.
Back to top
guntony



Joined: 23 May 2008
Posts: 7
Location: Hertfordshire

PostPosted: Sun May 25, 2008 6:36 pm    Post subject: Reply with quote

Many thanks for all your help. I'll post a note to let you know whether I'm fixed or not.

Cheers.....
Back to top
zubsgela



Joined: 15 May 2008
Posts: 9
Location: Blackburn, UK

PostPosted: Wed May 28, 2008 10:57 am    Post subject: Reply with quote

guntony wrote:
I'll post a note to let you know whether I'm fixed or not


Im sure we on about the boiler, Whats wrong in you that needs fixing my mates a doctor,
Back to top