Gate Valves on combi boiler flow and return pipes

 
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Plumber
Author Message
turtle1963



Joined: 04 May 2008
Posts: 4
Location: Crawley

PostPosted: Sun May 04, 2008 9:36 am    Post subject: Gate Valves on combi boiler flow and return pipes Reply with quote

Hi,

Can anyone tell me whether or not it is permissioble to put gate valves (with turn handle still intact) on the central heating flow and return pipes just beneath the boiler.

I have been told various things from various parties ranging from this is inadvisable to this is highly dangerous and illegal.

Thanks
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4249
Location: Bath

PostPosted: Mon May 12, 2008 8:07 pm    Post subject: Reply with quote

Just notice this post Shocked

Do you mean lever ball valves with turn handles or lockshield gate valves that don't have handles.

Any combi boiler I have seen has valves supplied with the mounting plate, also they have flow switches with will prevent the boiler working if there's no circulation through the HX.

I can't really see a problem at all, and if it's illegal I've installed a lot of illegal boilers over the last 49.4 years