Ask the Question Forum Index Ask the Question
FREE question and answer forums in a variety of subjects
 
 FAQFAQ   SearchSearch   UsergroupsUsergroups   RegisterRegister 
 ProfileProfile   Log in to check your private messagesLog in to check your private messages   Log inLog in 

Central Heating Problems
Goto page Previous  1, 2
 
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Plumber
Author Message
ChrisR
Moderator


Joined: 18 Feb 2003
Posts: 87
Location: Surrey/London border, UK

PostPosted: Thu Feb 28, 2008 5:33 pm    Post subject: Reply with quote

Optia looks like an Ideal Classic. Manual in the ether John.

I expect the HW circuit is such low resistance that it knobbles the pressure available from the pump, so the circulation downstairs just stops.
Needs a gate valve on the HW primaries to balance it.
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4659
Location: Bath

PostPosted: Thu Feb 28, 2008 5:59 pm    Post subject: Reply with quote

Cheers Chris, yes it does look like the classic, but when I do an google it shows then for sale but nothing on the ideal site Confused

So you reckon the primary's to the cylinder is pinching 90% of the water when the valve is in the mid position.

Yes could well do, and that would leave little to no flow to the ground floor.

An lockshield gate valve on the cylinder return and just crack it open then Cool
Back to top
Yellowman



Joined: 03 Jan 2008
Posts: 79
Location: Sussex

PostPosted: Thu Feb 28, 2008 11:42 pm    Post subject: Reply with quote

What Chris is saying makes sense. The problem has only been introduced since the addtion of 10mm pipework so im pretty sure he's right.

What you really need to do is put central heating only on and try balancing the rads first by turning the upstairs one down a bit.

Then introduce a gate valve on the cylinder return pipe. Once you have the Ch balanced you can turn on both HW and Ch and begin to close the gate valve on the HW return until the HW side of the system no longer draws heat away from the downstairs rads.
Back to top
Ash



Joined: 25 Feb 2008
Posts: 11
Location: Hull

PostPosted: Fri Feb 29, 2008 1:51 pm    Post subject: Reply with quote

Thanks to all for your suggestions. I have something to put to the plumber when he returns. Unfortunately the guy who installed the boiler did not do the work on the radiators so there is a difference of opinion as to who or what may be the cause of the problem.
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4659
Location: Bath

PostPosted: Fri Feb 29, 2008 1:59 pm    Post subject: Reply with quote

The problem will be with the system not the boiler
Back to top
Ash



Joined: 25 Feb 2008
Posts: 11
Location: Hull

PostPosted: Thu Mar 13, 2008 12:50 pm    Post subject: Reply with quote

The plumber returned yesterday. Fitted a new diverter valve and checked connections. He is adamant that it's connected OK and that there was nothing wrong with the original installation.

I've had a go at balancing the system and this seems to have improved the situation regarding the time taken for the downstairs radiators to warm up. They are now hot in 5 - 10 minutes. Upstairs radiators are taking longer to warm up now though. Maybe I need to slightly adjust the flow to these.

There is a valve on the hot water cylinder return valve which I have closed slightly from its original position. I noticed this morning that the system is now much noisier. Especially the pipes in the airing cupboard where the hot water cylinder, pump, diverter valve are located. The noise appears to occur when the pump is working. Sounds much like a seashell type sound in the pipes. Any ideas would be much appreciated.
Back to top
Yellowman



Joined: 03 Jan 2008
Posts: 79
Location: Sussex

PostPosted: Thu Mar 13, 2008 3:33 pm    Post subject: Reply with quote

Does this sound go when open the gate valve back up on the cylinder return pipe? If may be that the water is making a rushing sound as when the valve is closed a bit it restrict the flow thorugh the coil within the cylinder.
Back to top
Ash



Joined: 25 Feb 2008
Posts: 11
Location: Hull

PostPosted: Thu Mar 13, 2008 3:59 pm    Post subject: Reply with quote

I closed the valve on the hot water return pipe very slightly, as suggested, in order to prevent the loss of heat in the downstairs radiators when the hot water is run. I will open the valve up again and see what happens. Although the noise is annoying can I assume that no damage is being caused to the system.

Thanks.
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4659
Location: Bath

PostPosted: Thu Mar 13, 2008 4:06 pm    Post subject: Reply with quote

When the noise is going on, check the MV is open to the heating, and manually open it if it isn't
Back to top
Ash



Joined: 25 Feb 2008
Posts: 11
Location: Hull

PostPosted: Thu Mar 13, 2008 4:16 pm    Post subject: Reply with quote

By MV do you mean the gate valve on the hot water cylinder return pipe or the diverter valve. If it's the diverter, how do I do this. I thought the diverter worked automatically.

Thanks.
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4659
Location: Bath

PostPosted: Thu Mar 13, 2008 4:34 pm    Post subject: Reply with quote

Ash wrote:
By MV do you mean the gate valve on the hot water cylinder return pipe or the diverter valve. If it's the diverter, how do I do this. I thought the diverter worked automatically.

Thanks.


It is not an diverter valve, its an flow share valve, on the end of the valve is an lever, slide it over and hook it in the slot.

Don't touch the gate valve for now
Back to top
Display posts from previous:   
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Plumber All times are GMT - 1 Hours
Goto page Previous  1, 2
Page 2 of 2

 




Powered by phpBB © 2001, 2005 phpBB Group
Web Advertising | Mortgage Calculator | Remortgages | Personal Injury Lawyer Los Angeles | Personal Loans