dave.k66
Joined: 10 Mar 2008 Posts: 4 Location: romford
|
Posted: Mon Mar 10, 2008 7:25 pm Post subject: boiler problem |
|
|
| I have an old potterton netaheat profile boiler that keeps triping the reset button i have recently changed the grunfos pump on the system but it seems to be a intermittent problem sometimes it stays on then another time it tripps after ten minuites it does not seem to want to work with the room stat so i have the stat turned up fully ... any help would be great thanks... |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4416 Location: Bath
|
Posted: Mon Mar 10, 2008 10:39 pm Post subject: |
|
|
Tripping is invariably an circulation problem.
If you are sure the pump work all the time then check any motorized valve, check the header tank has water in it. after that suspect the system is sludged up.
Please remember the netaheat is an dangerous boiler if you are not competent. |
|
| Back to top |
|
 |
dave.k66
Joined: 10 Mar 2008 Posts: 4 Location: romford
|
Posted: Wed Mar 12, 2008 5:31 pm Post subject: |
|
|
| Thanks thats a help because i know there is a lot of sludge in the system from when i drained it once thanks again |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4416 Location: Bath
|
Posted: Wed Mar 12, 2008 6:17 pm Post subject: |
|
|
| Do let us know what you find please. |
|
| Back to top |
|
 |
|