Joined: 24 Feb 2003 Posts: 18 Location: South London / North Surrey
|
Posted: Mon Nov 05, 2007 10:40 pm Post subject: Bonding to gas and water |
|
|
| I have just checked the MET and see that the bonding to the gas inlet is 16mm whilst the water is somewhat less than 10mm. No obviously I need to uprade the water bonding, but to 10mm or 16mm? |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4401 Location: Bath
|
Posted: Mon Nov 05, 2007 10:53 pm Post subject: |
|
|
| Unless they changed it again, which wouldn't surprise me, the gas is 10mm |
|
| Back to top |
|
 |
vince knight Moderator
Joined: 04 Mar 2004 Posts: 1274 Location: Essex/East London
|
Posted: Mon Nov 05, 2007 11:12 pm Post subject: |
|
|
10mm is the norm for gas and water.
They are to be bonded to within 600mm of the stopcock on the customer side or where they enter the building.
Vince |
|