Bonding to gas and water

 
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Electrician
Author Message
DJM



Joined: 24 Feb 2003
Posts: 18
Location: South London / North Surrey

PostPosted: Mon Nov 05, 2007 10:40 pm    Post subject: Bonding to gas and water Reply with quote

I have just checked the MET and see that the bonding to the gas inlet is 16mm whilst the water is somewhat less than 10mm. No obviously I need to uprade the water bonding, but to 10mm or 16mm?
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4401
Location: Bath

PostPosted: Mon Nov 05, 2007 10:53 pm    Post subject: Reply with quote

Unless they changed it again, which wouldn't surprise me, the gas is 10mm
Back to top
vince knight
Moderator


Joined: 04 Mar 2004
Posts: 1274
Location: Essex/East London

PostPosted: Mon Nov 05, 2007 11:12 pm    Post subject: Reply with quote

10mm is the norm for gas and water.
They are to be bonded to within 600mm of the stopcock on the customer side or where they enter the building.

Vince
Back to top