peter Hofman
Joined: 18 Apr 2008 Posts: 2 Location: lincolshire
|
Posted: Tue Apr 22, 2008 10:39 pm Post subject: Overflowing F&E tank |
|
|
I have a 'Boulter Buderos' oil fired boiler. It is a fully pumped open vented system with a 3 port valve and is about 4 years old. It has been running without any problems.
My problem started when the overheat thermost kept cutting in and water overflowed from the F&E tank. I had the boiler checked by Boulter and they stated that the boiler was ok and that there must be a problem on the rest of the system. I don' know how old the rest of the system is.
I have de- sludged the system but the problem persists.
When I check the F&E tank the water is to the top and is warm.
This overflow is not a great deal and only seems to happen in the mornings after the boiler has been on for about an hour. In the evenings I have to reset the overheat thermostat andall evening there is no problem
The pump and the diverter valve have been checked and appear to be working O.K
I wonder if you could give this some thought and advise me as to what the problem may be and my next course of action
Yours
FRUSTRATED OF Spalding |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4249 Location: Bath
|
Posted: Tue Apr 22, 2008 10:51 pm Post subject: |
|
|
What model is it.
Does it play up in the hot water mode as well |
|
| Back to top |
|
 |
peter Hofman
Joined: 18 Apr 2008 Posts: 2 Location: lincolshire
|
Posted: Wed Apr 23, 2008 2:25 pm Post subject: F&E overflowing |
|
|
Scruff,
The modle is a Camray 5--65/90A.I have again flushed the sytem throug
h which to me was pretty clear, no heavy staining of the water.
'Tried the system out in H?W only and no problem. I ran it in cojunction with the C/H for about one hour and switched the heating off leaving just the H/W control on by the clock. After about 10 mins I saw hot water and steam being pumped into the F&E tank via the vent pipe. The tank filled and the excess water went out of the overflow. This was not a great amount, but I am once again left with a tank full of very warm water.
Where the hell does this excess of water come from?
I can not see any discolouration of the water at any taps in the bungalow.
I did hear in the boiler what appeared to be rushing and gurgling sound after I had turned off the C/H. Steam possibly?
Thank you for a very prompt reply.
Cheers Peter |
|
| Back to top |
|
 |
AlanE Moderator
Joined: 29 Jun 2003 Posts: 1131 Location: Colchester Essex
|
Posted: Wed Apr 23, 2008 7:01 pm Post subject: |
|
|
| Check the boiler thermostat or just change it they are cheap enough. I've changed several on the Camray 5 range for overheating problems. |
|
| Back to top |
|
 |
|