dodgy rad?

 
Post new topic   Reply to topic    Ask the Question Forum Index -> Ask the Plumber
Author Message
MarinaH



Joined: 15 Aug 2005
Posts: 3
Location: London

PostPosted: Tue Mar 11, 2008 9:20 am    Post subject: dodgy rad? Reply with quote

I’ve had a new boiler installed 2 weeks ago, it’s a combi Worcester Bosch Greenstar 28i junior. it's been working ok, then yesterday I noticed the room thermostat, whihch is set to 23 degrees, was struggling to go up & had stopped at 20 degrees.

One of the radiators in the room was lukewarm, so thought it could be a balance problem, turned dow a couple of rads and put the dodgy one on maximum. It heated up within half an hour and was as hot as all the other rads and the room thermostat went up to 21 degrees. Let the heating on all night and this morning woke up to find the thermostat STILL at 21 degrees and the lukewarm rad STILL lukewarm tho it’s on maximum!

Any ideas????

thanks
Back to top
straker1966



Joined: 06 Jan 2008
Posts: 164
Location: cambridge

PostPosted: Tue Mar 11, 2008 6:25 pm    Post subject: Re: dodgy rad? Reply with quote

1. is the radiator big enough?
2. how drafty is the house? is all the heat flying out the windows?
3. is the heating on long enough?
4. is the boiler stat on a high enough setting?
5. does the radiator have a thermostat?
6. is the room thermostat near a draft? could be in the wrong place.
Back to top
MarinaH



Joined: 15 Aug 2005
Posts: 3
Location: London

PostPosted: Wed Mar 12, 2008 11:05 am    Post subject: Re: dodgy rad? Reply with quote

straker1966 wrote:
1. is the radiator big enough?
Yes
2. how drafty is the house? is all the heat flying out the windows?
not very - radiator away from windows
3. is the heating on long enough?
it's been on Constant for the past few days
4. is the boiler stat on a high enough setting?
yes - on maximum
5. does the radiator have a thermostat?
No
6. is the room thermostat near a draft? could be in the wrong place.
No


the rad's now completely cold - I think the valve's gone.
thanks for your reply.
Back to top
thescruff
Moderator


Joined: 03 May 2003
Posts: 4400
Location: Bath

PostPosted: Wed Mar 12, 2008 11:17 am    Post subject: Reply with quote

Check and open the lockshield valve a turn. Turn the lockshield valve on all the hot rads down a turn.

Remove the thermostatic head and check the pin is free to go up and down, give it a squirt of WD40.

Leave the head off and see if the radiator gets hot.
Back to top