allmond
Joined: 17 Dec 2002 Posts: 1
|
Posted: Tue Dec 17, 2002 10:25 pm Post subject: Overpumping |
|
|
Just occasionally my central heating pumps excess water up the expansion pipe into the header tank. Not good as it leads to steam in the loft!! The pump is set at the lowest speed. I have experimented and can solve the problem by partially closing the gate valve above the pump, but this is obviously not a permanent solution.
Any help appreciated.
Jamie |
|
| Back to top |
|
 |
GEORGE COTTRELL
Joined: 17 Jan 2003 Posts: 2
|
Posted: Fri Jan 17, 2003 2:25 pm Post subject: |
|
|
| I have had this problem also, have found that the air may not be venting properly, the last radiator(might be the first) acts as a vent to the expansion tank, check to see if there is any air trapped in radiator. |
|