Posted: Tue Jun 24, 2008 9:07 pm Post subject: Where in the NEC... |
|
|
What part of nec2008 covers signal wiring, such as process control signals to/from a PLC? ...and also information about such signals sharing conduits with power circuits?
prjm |
|
| Back to top |
|
 |
vince knight Moderator
Joined: 04 Mar 2004 Posts: 1290 Location: Essex/East London
|
Posted: Wed Jun 25, 2008 9:07 pm Post subject: |
|
|
One for 'B' to answer I think as he is on your side of the pond  |
|
| Back to top |
|
 |
b Moderator
Joined: 31 Aug 2004 Posts: 301 Location: michigan
|
Posted: Fri Jun 27, 2008 5:50 pm Post subject: |
|
|
I believe you are looking for article 645 in the NEC. You are not allowed to share a conduit with power and signal circuitry. In addition to the safety factor of getting the wrong wire... there is also concern of induced voltage on the signal circuit.