streety
Joined: 21 Sep 2003 Posts: 1 Location: uk
|
Posted: Sun Sep 21, 2003 10:12 am Post subject: Poor central heating circulation-position of pump or pipes? |
|
|
The circulation of my central heating is not great. Either the thermostat of the boiler kicks in, or if I turn up the thermostat I have to regularly bleed the radiators to let air out that presumably is caused by the water virtually boiling. Turning the pump up to top speed does not rectify this.
The system was new when I moved in, but I have flushed the system and it isn't clogged. The pump is situated on the flow pipe prior to the 3 way valve. I have tried moving it directly after the boiler, but this just succeeded in shooting hot water out of the top of the system into the feed and expansion tank!
Is the position of the pump likely to be a factor or more likely to be the layout of the pipework? (There is a branch to a radiator that branches off from the main 'loop' of the pipework)
Any thoughts anyone might have would be appreciated. |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4417 Location: Bath
|
Posted: Sun Sep 21, 2003 10:35 am Post subject: |
|
|
Sounds like its all wrong.
Send a sketch to scruff2@blueyonder.co.uk
scruff.  |
|
| Back to top |
|
 |
DP
Joined: 08 Sep 2003 Posts: 26 Location: Glasgow
|
Posted: Sun Sep 21, 2003 11:42 am Post subject: |
|
|
Relocate pump to original position. A new boiler means you should have manufacturer's instruction manual as well as a Benchmark Logbook. This logbook will tell you what chemicals and treating agents were used when new boiler was fitted. It should also tell you if the boiler and installation has been set up to maker's requirements. Chances are you will not find this logbook as system was not treated.
System debris is likely to be the cause of poor operation.
Are all the rads failing to heat up? |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4417 Location: Bath
|
Posted: Sun Sep 21, 2003 12:10 pm Post subject: |
|
|
Sounds more like bad design to me DP.
scruff.  |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4417 Location: Bath
|
Posted: Sun Sep 21, 2003 12:59 pm Post subject: |
|
|
Definitely a problem with the system, who fitted it.
I will update your drawing a bit, more info will be required.
scruff.  |
|