vauxy
Joined: 31 Aug 2003 Posts: 2 Location: england
|
Posted: Sun Aug 31, 2003 8:00 pm Post subject: hot water/central heating problems |
|
|
| hi,my problem is that the radiators are working on my hot water/central heating system even though the heating is turned off for the summer.it has only started doing this today.the system is one with a seperate copper water cylinder and a standard boiler,any help greatly appreciated |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4476 Location: Bath
|
Posted: Sun Aug 31, 2003 8:23 pm Post subject: |
|
|
At this stageit could be anything, need to know more about controls like motorized valves room stats etc.
scruff.  |
|
| Back to top |
|
 |
vauxy
Joined: 31 Aug 2003 Posts: 2 Location: england
|
Posted: Sun Aug 31, 2003 8:31 pm Post subject: |
|
|
| its a danfoss 3 way valve,the room stat seems to be ok,could the valve be stuck in between two pipes and that is what is causing the problem thanks |
|
| Back to top |
|
 |
thescruff Moderator
Joined: 03 May 2003 Posts: 4476 Location: Bath
|
Posted: Sun Aug 31, 2003 9:17 pm Post subject: |
|
|
Could be, check the valve for operation by turning the room stat up and down, check also the programmer is not sending a signal to the valve, turn the hot water stat down does the valve travel to one side and back when turned up.
Final check is there a frost stat thats bring it on.
scruff |
|